With energy costs being paramount to the majority of organisations, renewed vigour must be applied to design reviews, utilising 35W CDM-T technology with comprehensive service/guarantees in place (35W CMH-TD available with extended life).

Use of daylight and occupancy sensors are being promoted at realistic costs. For back of house, T5 lighting schemes are now a competitive option to T8 installations both in capital and running costs.

Lumen depreciation and dust - lighting levels increased by 50% with new lamps and reflector clean - a fact, minimizing the need for additional luminaires to be installed.

Lighting maintenance reduces capital investment and energy costs. Over specification is unnecessary with today's lamp technology, given maintenance regimes are in place within 12 months of installation.

Energy Consumption Data

Fluorescent Lamps

Lamp Type/Stated Wattage Initial Lumens Useful Life (Hours) EM Class 2 Rated Circuit Watts HF/Electronic Pre-2008 Rated Circuit Watts HF/Electronic Current (2011) Rated Circuit Watts
T5 14W HE (549) 1,230 20,000 N/A N/A 14.0 16.0 14.0 16.0
T5 21W HE (849) 1,910 20,000 N/A N/A 20.6 22.5 20.6 22.5
T5 28W HE (1149) 2,640 20,000 N/A N/A 27.9 30.5 27.9 30.5
T5 35W HE (1449) 3,320 20,000 N/A N/A 35.5 38.5 35.5 38.5
T5 24W HO (549) 1,750 20,000 N/A N/A 22.5 26.0 22.5 25.7
T5 39W HO (849) 3,200 20,000 N/A N/A 38.0 41.0 38.0 40.4
T5 49W HO (1449) 4,450 20,000 N/A N/A 49.2 52.5 49.2 52.5
T5 54W HO (1149) 4,460 20,000 N/A N/A 54.1 57.5 54.1 57.5
T5 80W HO (1449) 6,450 20,000 N/A N/A 80.0 86.0 79.8 85.8
T8 18W (600) 1,350 12,000 18 26.0 16.0 18.0 16.0 18.2
T8 30W (900) 2,450 12,000 30 38.0 N/A N/A 24.0 28.0
T8 36W (1200) 3,350 12,000 36 43.0 32.0 35.0 32.0 35.0
T8 58W (1500) 5,200 12,000 58 67.0 50.0 54.0 50.0 54.0
T8 70W (1800) 6,300 12,000 70 80.0 60.0 68.0 60.0 65.6

Compact Fluorescent Lamps

Lamp Type/Stated Wattage Initial Lumens Useful Life (Hours) EM Class 2 Rated Circuit Watts HF/Electronic Pre-2008 Rated Circuit Watts HF/Electronic Current (2011) Rated Circuit Watts
Biax D 10W 600 12,000 10 16.0 9.5 12.0 9.0 11.5
Biax D 13W 900 12,000 13 19.0 11.2 15.8 14.0 18.0
Biax D 18W 1,200 12,000 18 26.0 16.5 19.5 15.5 19.0
Biax D 26W 1,800 12,000 26 34.0 24.0 26.5 20.5 24.0
Biax L 18W 1,250 8,000 18 26.0 16.0 18.5 14.0 16.5
Biax L 24W 1,800 8,000 24 32.0 22.0 25.0 21.5 24.0
Biax L 36W 2,900 8,000 36 43.0 32.0 33.8 32.0 33.8
Biax L 40W 3,500 8,000 N/A N/A 40.0 44.1 40.0 44.1
Biax L 55W 4,800 8,000 N/A N/A 55.0 61.0 55.0 61.0
Biax T 18W 1,200 12,000 18 26.0 16.5 19.5 15.5 19.0
Biax T 26W 1,800 12,000 26 34.0 24.0 26.5 24.0 26.5
Biax T 32W 2,400 12,000 N/A N/A 32.0 34.5 32.0 34.5
Biax T 42W 3,200 12,000 N/A N/A 42.0 46.0 42.0 46.0
Biax T 57W 4,300 12,000 N/A N/A 57.5 60.5 57.5 60.5
Biax 2D 16W 1,100 10,000 16 23.0 N/A N/A 14.0 18.0
Biax 2D 21W 1,375 10,000 21 29.0 N/A N/A
Biax 2D 28W 2,150 12,000 28 36.0 25.4 28.7 25.4 28.7
Biax 2D 38W 3,000 12,000 38 45.0 34.6 39.7 34.6 39.7
Biax 2D 55W 3,900 8,000 N/A N/A 53.0 60.0 53.0 60.0

Discharge Lamps

Lamp Type/Stated Wattage Initial Lumens Useful Life (Hours) EM Class 2 Rated Circuit Watts HF/Electronic Pre-2008 Rated Circuit Watts HF/Electronic Current (2011) Rated Circuit Watts
Super Mini (GU6.5) CMH 20W (830) 1,615 6,000 N/A N/A 20 24.5 20.0 23.0
Super Mini (GU6.5) CMH 35W 3,400 6,000 N/A N/A 39 45.0 39.0 43.5
CMH-TC (G8.5) 20W (830) 1,650 8,000 N/A N/A 20 24.5 20.0 23.0
CMH-TC (G8.5) 35W 3,200 8,000 35 43.6 39 45.0 39.0 43.5
CMH-TC (G8.5) 70W 6,200 8,000 75 90.7 72 80.0 73.0 79.0
CMH-T (G12) 20W (830) 1,650 8,000 N/A N/A 20 24.5 20.0 23.0
CMH-T (G12) 35W 3,200 12,000 35 43.6 39 45.0 39.0 43.5
CMH-T (G12) 70W 6,200 12,000 75 90.7 72 80.0 73.0 79.9
CMH-T (G12) 150W 13,000 8,000 150 174.0 147 160.0 147.0 158.5
CMH-TD (RX7s) 35W (830) 3,400 12,000 35 43.6 39 45.0 39.0 43.5
CMH-TD (RX7s) 70W 6,200 12,000 75 90.7 72 80.0 73.0 79.9
CMH-TD (RX7s) 150W 12,500 12,000 150 174.0 147 160.0 147.0 158.5
CMH-MR16 (GX10) 20W (830) Ref. to Cat. 6,000 N/A N/A 20 24.5 20.0 23.0
CMH-MR16 (GX10) 35W (830) Ref. to Cat. 6,000 N/A N/A 39 45.0 39.0 43.5
CMH PAR 30 (E27) 20W Ref. to Cat. 8,000 N/A N/A 20 24.5 20.0 23.0
CMH PAR 30 (E27) 35W Ref. to Cat. 8,000 35 43.6 39 45.0 39.0 43.5
CMH PAR 30 (E27) 70W Ref. to Cat. 8,000 75 90.7 72 80.0 73.0 79.0
CMH E (E27) 70W 5,300 12,000 75 90.7 72 80.0 73.0 79.0
CMH E (E27) 100W (830) 8,700 12,000 100 113.7 99 110.0 100.0 108.0
CMH E (E27) 150W 12,300 12,000 150 174.0 147 160.0 147.0 158.5
CMH-T (E40) 150W 12,500 12,000 150 174.0 147 160.0 147.0 161.0
CMH-T (E40) 250W 20,000 12,000 250 275.5 N/A N/A 252.0 275.0
CMH-T (E40) 400W 41,000 12,000 400 429.8 N/A N/A N/A N/A